8 Channel Current Analog Input Safety Module SIL 3
Model:UW5932S
UW5932S 8 Channel Current Analog Input Safety Module SIL 3 from China supplier UWNTEK implements data conversion, comprehensive diagnosis, digital filtering, linear correction, engineering conversion, safe voting and other functions of 8-channel 4~20mA analog input signals, achieving high reliability, high availability, high security, Strong adaptability design.
8 Channel Current Analog Input Safety Module SIL 3 Functional features
The system automatically identifies the module type and enables plug-and-play;
The 8 Channel Current Analog Input Safety Module SIL 3 adopts 1oo2D architecture, with 2 sets of channels for independent sampling and hardware diagnosis, and output after safe voting;
The channel adopts independent ADC chip sampling, which has the characteristics of high precision and high stability;
Complete electrical isolation between the module and the system, completely shutting out external interference;
PhotoMos switch switches scanning channels, and channels are isolated from each other. When a channel fails, it will not affect the normal operation of other channels;
Supports signal data transformation, channel input diagnosis, digital filtering, linear correction, engineering conversion and other functions;
It is used for safety loops and has relatively complete module fault diagnosis functions, including power supply circuit over- and under-voltage diagnosis, channel fault diagnosis, ADC fault diagnosis, main crystal oscillator diagnosis and other hardware diagnostic functions, as well as CPU diagnosis (general register diagnosis, stack pointer diagnosis, Software diagnostic functions such as RAM diagnosis, Flash diagnosis, etc.), interrupt diagnosis, communication diagnosis, peripheral driver diagnosis, etc.;
When the module diagnoses a fault, the system quickly responds to the safety action corresponding to the fault to ensure production safety;
8 Channel Current Analog Input Safety Module SIL 3 Technical parameters
parameter name
Technical indicators
Channel configuration
8
Analog input
4~20mA
Analog sampling
±0.1%F.S
Common mode rejection
≥110dB
Series mode interference
≥60dB
Isolation impedance
≥20MΩ@500V
Security system capabilities
SC3
security integrity
SIL3
safety accuracy
±5%F. S
Safety circuit failure diagnosis
Open circuit, short circuit, transmitter failure
redundancy mechanism
Hot standby 1:1 redundancy (optional), supports hot swap