The UW5915S 16-Channel Digital Level Input Safety Module SIL 2 from China supplier implements functions such as input filtering, comprehensive diagnosis, time stamping, and safe voting for 16-channel level input signals, achieving high reliability, high availability, high security, and strong adaptability design.

Features:

The system automatically identifies the module type and enables plug-and-play;


The 16-Channel Digital Level Input Safety Module SIL 2 adopts 1oo1D architecture and can support 1oo2D architecture through redundant configuration;


Photoelectric isolation is used between the signal and the system, with an isolation voltage of 2000V;


Channels are isolated from each other, and channel failure does not affect the normal operation of other channels;


Supports channel input filtering, channel input diagnosis and other functions;


 It is used for safety loops and has relatively complete module fault diagnosis functions, including power supply circuit over- and under-voltage diagnosis, channel fault diagnosis, channel safety failure diagnosis, main crystal oscillator diagnosis and other hardware diagnostic functions, as well as CPU diagnosis (general register diagnosis, stack pointer diagnosis , RAM diagnosis, Flash diagnosis, etc.), interrupt diagnosis, communication diagnosis, peripheral driver diagnosis and other software diagnostic functions;


When the module diagnoses a fault, the system quickly responds to the safety action corresponding to the fault to ensure production

Safety.


Technical Parameters:

parameter name Technical indicators
Channel configuration 16 level signal inputs
Scan cycle 5ms
Logic 1 (minimum) Contact level 18~30VDC
Logic 0 (maximum) Contact level 0~5VDC
Security system capabilities SC2
security integrity SIL2
Safety circuit failure diagnosis open circuit, short circuit
redundancy mechanism Hot standby 1:1 redundancy (optional), supports hot swap
EMC electromagnetic and EN61326-3-1 (ESD/RS/EFT/SURGE/CS/DIP/CE/RE), Level 3a
capacitive 118mm×32mm×112mm
Module size 0.8W
Power consumption -20℃~70℃
Operating temperature UW5971S 4-unit input and output terminal block
UW5971S_ F DI relay isolation contact safety input terminal block
Correspondence between terminals and channel codes in hardware configuration software
IO-0 Terminal label 00A PV0- 00B PV0- ...... 07A PV0- 07B PV0-
channel coding 00 01 ...... 14 15
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
IO-3 Terminal label 30A PV3- 30B PV3- ...... 37A PV3- 37B PV3-
channel coding 00 01 ...... 14 15






Hot Tags: 16-Channel Digital Level Input Safety Module SIL 2, China, Manufacturer, Supplier, Factory, Wholesale, Quality, Price